Low voltage cabling for commercial buildings

Beyond the data network, a building runs on low-voltage cable: door hardware, AV, paging, intercoms and sensors. Cablify runs and labels it to the same standard as the network cabling, so every system has a record.

How the NEC sorts low-voltage systems

Low voltage is a trade term. The National Electrical Code sorts these systems by what they carry, and each has its own article for cable types, ratings and installation.

SystemExamples2023 NEC
CommunicationsVoice, data and coaxial TV cableArticles 800 and 805
Optical fiberBackbone and campus fiberArticle 770
Class 2 and Class 3 circuitsDoor hardware, thermostats, sensors, many AV control circuitsArticle 725, with cable rules in Article 722
Class 1 circuitsSome control and signaling circuitsArticle 724
Fire alarmDetection and notification circuitsArticle 760
AudioPaging and sound systemsArticle 640
Class 4 fault-managed powerA newer way to deliver power over cableArticle 726
The 2026 NEC reorganizes these articles again, adding Article 720 for limited-energy systems and deleting Articles 770, 805 and 840. Each jurisdiction adopts an edition on its own schedule, and the inspector works from that edition.

Class 2 limits and separation

Class 2 is the circuit type behind much of the door hardware, sensors and controls in a building. At 30 volts or less, a Class 2 power supply is limited to 100 VA. That limit is what lets Class 2 cable be installed without the wiring methods power circuits need.

Class 2 and 3 cable has to stay at least 2 inches from power and Class 1 conductors unless a barrier or raceway separates them, under NEC 725.136. Sharing a conduit with power is not allowed as a rule.

  • Separate pathways from line-voltage wiring
  • Cable listed for the space: plenum, riser or general purpose
  • Supported from the building structure
  • Labeled at both ends and recorded with the system it serves
  • Firestopping restored at every rated penetration

Systems we cable

We run, terminate and label the cable for these systems. The system vendor or your integrator programs the equipment.

Door hardware

Electrified locks, exit devices, door contacts and automatic operators. See access control.

AV and conference rooms

Display, camera, control panel and table connection cable, with pathways to the AV rack.

Paging and background audio

Speaker cable to ceiling and horn speakers, zoned the way the building is used.

Intercom and video entry

Door stations, master stations and the cable to the gate or lobby.

Sensors and controls

Thermostats, occupancy sensors and other building control devices on Class 2 circuits.

Radio coverage pathways

Riser and ceiling pathways for in-building radio and cellular systems. See commercial real estate.

Licensing differs by state

There is no national low-voltage license. These are examples from state licensing bodies; cities can add their own rules, and we confirm what applies when we scope the job.

StateLicensing bodyClassificationWhat it covers
CaliforniaContractors State License BoardC-7 Low Voltage SystemsEnergy-limited systems not exceeding 91 volts; low-voltage fire alarm is excluded
GeorgiaDivision of Low-voltage ContractorsLV-A, LV-T, LV-G, LV-UAlarm, telecommunications, general and unrestricted low-voltage work
North CarolinaBoard of Examiners of Electrical ContractorsSP-FA/LVSpecial restricted fire alarm and low-voltage work
WashingtonDepartment of Labor and Industries06 Limited energy systemSignaling and power-limited circuits; the 09 telecommunications specialty excludes access control and intrusion alarms
FloridaElectrical Contractors’ Licensing BoardLimited Energy Systems SpecialtySystems up to 98 volts RMS, excluding alarm work, which needs an alarm system contractor license
TexasDepartment of Public Safety, Private Security ProgramAlarm and access control company licensingAlarm, CCTV and electronic access control installers; a state electrician license is not required for Class 1, 2 or 3 circuits
Summarized from each state’s licensing rules. Check the current rules with the state before relying on this table.

Common questions

What counts as low voltage?

It depends on who is asking. The NEC uses circuit classes, such as Class 2, rather than one voltage. State licenses draw their own lines: California’s C-7 covers energy-limited systems up to 91 volts, and Florida’s limited energy specialty goes up to 98 volts RMS.

Do you need a license for low voltage wiring?

In many states, yes, and the license depends on the system. Some states license low-voltage work broadly, some license only alarm and access control installers, and some leave it to cities. We check the rules for your state and city before the job.

Can low voltage cable share a conduit with power?

Not as a rule. The NEC requires Class 2 and Class 3 cable to be separated from power and Class 1 conductors, with limited exceptions such as a listed barrier.

What is a Class 2 circuit?

A power-limited circuit defined by the NEC. At 30 volts or less, the power source is limited to 100 VA, which keeps the shock and fire risk low enough for lighter wiring methods.